Siemens SIRIUS 3RH2 Contactor Relay - 6NO + 2NC, 24V DC

The Siemens SIRIUS 3RH2 contactor relay is designed for control circuit signal switching in size S...

Best current price£33.28from Rapid Online - Rapid Electronics Ltd.

All Offers

19 offers from £33.28 - £91.20

View price history by clicking the chart icon.

Rapid Online - Rapid Electronics Ltd.Siemens 3RH2122-2AP00 Auxiliary Contactor railway 2NO+1NC 24V DC PLC
Free delivery in 1–3 days
£33.28
Visit shop
Tameson UKSiemens 3Rh2140 4No Contactor Relay 24V Dc S00 - 3Rh21402bb40
Free delivery in 1–3 days
£38.82
Visit shop
eBaySIRIUS 3RT 3RH
£13.20 delivery
£65.28
Visit shop

Used Offers

10 offers from £9.44 - £20.66

View price history by clicking the chart icon.

eBaySIEMENS 3RH2122-2BB40, Contactor relay, E06 - Broken holding lugs
£29.14 delivery
£9.44
Visit shop

Product Information

Full details

The Siemens SIRIUS 3RH2 Contactor Relay is designed for control circuit signal switching in size S00 industrial applications. It offers a robust solution for reliable control by providing 6 normally open (NO) and 2 normally closed (NC) contacts operated by a 24V DC coil. While it delivers dependable switching and expandable pole configurations, users should be aware of its specific coil voltage requirement.

All features

SeriesSIRIUS
Model Part Number3RH2262-1BB40
BrandSiemens

Extended Product Information

FAQs

What is the coil voltage for this Siemens SIRIUS 3RH2 contactor relay?

This specific model (3RH2262-1BB40) operates with a 24V DC coil voltage.

How many normally open (NO) and normally closed (NC) contacts does this relay have?

It features 6 normally open (NO) and 2 normally closed (NC) contacts.

Can I add more contacts to this relay?

Yes, the auxiliary switches are expandable, allowing you to increase the total pole count from 4 to 8 by adding auxiliary switch modules.

What type of terminals does this relay use?

This relay is equipped with screw terminals for secure electrical connections.

What certifications does this product hold?

The Siemens SIRIUS 3RH2 series holds worldwide certifications including IEC and UL/CSA.

Is this relay suitable for direct motor starting?

No, this is a contactor relay designed for control circuit signal switching. It is not intended for directly switching motor power loads, which typically require power contactors.

What does 'positively driven operation' mean?

Positively driven operation means that if an NC contact is welded shut, the corresponding NO contact cannot close, and vice-versa. This is a crucial safety feature for certain control applications.

Troubleshooting

Contactor relay does not energize (no click sound)

Verify the 24V DC control supply voltage is present at the coil terminals (A1/A2). Check wiring connections for looseness or errors. Ensure the control signal is active.

Contacts are stuck in either the NO or NC position

Ensure the coil is de-energized if it should be open, or energized if it should be closed. Check for any physical obstructions. If the issue persists, the relay may be damaged and require replacement.

Intermittent operation or poor connection

Check and re-tighten all screw terminal connections. Ensure the mounting is secure and the relay is properly seated on the DIN rail. Inspect wiring for damage.

Overheating at terminals

Immediately de-energize the circuit. Check terminal tightness, as loose connections are a common cause. Ensure the wire gauge is appropriate for the current being carried. Replace if signs of melting or charring are present.

Pros and Cons

Pros

  • Reliable signal switching for control circuits.
  • Expandable contact configuration offers flexibility.
  • Standard terminal designations simplify wiring.
  • Positively driven operation enhances safety.
  • Global certifications ensure broad applicability.

Cons

  • Requires a specific 24V DC coil voltage; not compatible with AC coils.
  • Size S00 may not be suitable for very high power applications.
  • Screw terminals require proper torque for secure connections.
  • Expansion of auxiliary switches requires additional components.

Setup, Compatibility & Care Instructions

Setup:

  1. Mounting: Mount the contactor relay onto a DIN rail or a suitable mounting plate in a control panel.
  2. Wiring: Connect the control circuit wiring to the coil terminals (A1/A2) with the specified 24V DC supply. Connect the load or control wires to the appropriate NO and NC terminals, ensuring correct polarity if applicable.
  3. Terminal Tightening: Securely tighten all screw terminals to the recommended torque to ensure a reliable connection and prevent overheating.
  4. Auxiliary Switch Addition: If expanding pole configuration, follow the specific instructions for attaching and wiring the additional auxiliary switch modules.

Compatibility:

  • Coil Voltage: This unit is designed for 24V DC coil operation. Ensure your control power source matches this specification.
  • Control Circuit: Suitable for use in standard industrial control circuits.
  • Mounting Standards: Compatible with standard 35mm DIN rails.
  • Certifications: IEC and UL/CSA certifications ensure compatibility with international electrical codes and standards.

Care:

  • Environment: Operate in a clean, dry environment. Avoid excessive dust, moisture, or corrosive atmospheres.
  • Cleaning: If necessary, clean the exterior with a dry or slightly damp cloth. Do not use solvents or abrasive cleaners.
  • Inspection: Periodically inspect terminals for tightness and signs of wear or corrosion.

Price History

DatePrice
Visit shop