Setup, Compatibility & Care
Setup: The GV2P22 is designed for direct mounting onto a 35mm DIN rail or panel mounting using a specific bracket. Ensure all power is disconnected before installation. Connect the main power conductors to the screw terminals, ensuring secure connections. The rated operating voltage is 0-690V. Set the overload release current by adjusting the rotary knob to the desired range (20-25A) based on the motor's full load amperage (FLA). The magnetic trip is factory-set but can be confirmed.
Compatibility: This breaker is suitable for three-phase motor applications up to 11kW at 400V. It is compatible with Schneider Electric TeSys components, such as contactors, for enhanced control and protection schemes. It adheres to multiple standards including IEC, UL, and CSA.
Care: Regularly inspect the device for any physical damage. Keep terminals clean and ensure all connections remain tight. The IP20 rating means it is protected against solid objects larger than 12.5mm but is not protected against water, so install it in a dry, clean environment. No internal maintenance is typically required for the thermal-magnetic trip unit.