The Legrand DX3 circuit breaker is designed for reliable electrical protection in residential and commercial applications. It offers robust performance with a 'C' release characteristic, making it suitable for circuits with moderate inrush currents, and its dual-pole configuration ensures comprehensive circuit isolation. A key caveat is its incompatibility with ground fault elements, requiring separate protection for ground fault detection. This guide will help you understand its features, setup, and maintenance.
| Series | DX3 |
|---|---|
| Model Part Number | 407740 |
| Brand | Legrand |
A Type 'B' breaker trips between 3-5 times its rated current, suitable for purely resistive loads. A Type 'C' breaker trips between 5-10 times its rated current, making it suitable for circuits with moderate inductive loads or inrush currents, like small motors or lighting transformers.
No, this specific Legrand DX3 circuit breaker model (407740) is not compatible with ground fault elements. You will need to install a separate Residual Current Device (RCD) or Ground Fault Circuit Interrupter (GFCI) upstream of this breaker if ground fault protection is required.
This breaker can accommodate multi-wired conductors from 0.75 to 10 mm² and solid-core conductors from 0.75 to 16 mm².
Auxiliary contacts for the DX3 series are designed to clip onto the side of the circuit breaker. Refer to the specific installation manual for the auxiliary contact model you are using, as wiring and mounting may vary slightly.
The IP20 rating signifies that the breaker is protected against solid objects larger than 12.5 mm (like a finger) and offers no protection against water. It should be installed in an enclosure to prevent accidental contact and exposure to moisture.
No, the IP20 rating indicates it is not protected against water ingress and is intended for indoor use within an electrical enclosure. Outdoor applications would require a higher IP rating and suitable environmental protection.
The rated short-circuit breaking capacity (Icn) according to EN 60898 at 230 V is 6 kA. The rated ultimate short-circuit breaking capacity (Icu) according to IEC 60947-2 at 230 V is 10 kA.
Check for overloaded circuits, excessive inrush current from connected devices, or potential short circuits. Verify conductor connections are secure and correctly sized. If the issue persists, consider if a higher-rated breaker or a different curve type is needed for the specific application, or if there's a fault within the connected equipment.
Ensure the fault condition that caused the trip has been resolved. Check that the toggle switch is fully in the 'OFF' position before attempting to reset. If it still won't reset, the breaker may be damaged and require replacement.
Verify that the main power supply is active. Check all incoming and outgoing conductor connections to the breaker for tightness. Test voltage at the breaker terminals to confirm power is present. If power is present at the terminals but not the circuit, the breaker itself may have failed internally.
Slight warmth can be normal under load, but excessive heat indicates a potential problem. Check for loose connections at the terminals, as this is a common cause of overheating. Ensure the breaker is not undersized for the continuous load. If heat persists, replace the breaker.