Schneider Electric Contactor - Acti9

Acti9 iCT modular contactor featuring 2-pole remote and manual control with 2 normally open contac...

Best current price£53.41from Tameson UK

All Offers

4 offers from £53.41 - £148.26

View price history by clicking the chart icon.

Tameson UKSchneider Electric Schneider Ict 25A 2No Modular Contactor 24Vac Manual - A9c21132
Free delivery in 1–3 days
£53.41
Visit shop
eBayModule Contactors 25A 2Z 0R 24V AC iCT A9C21132 Acti9
£13.20 delivery
£93.50
Visit shop

Product Information

Full details

This guide is for electricians and automation professionals who need reliable control of lighting, small motors, and HVAC systems. The Acti9 iCT modular contactor offers flexible remote and manual control with two normally open contacts, ensuring efficient operation. A key caveat is its specific coil voltage requirement, which must match the control circuit.

All features

SeriesActi9
Model Part NumberA9C21132
BrandSchneider Electric

Extended Product Information

FAQs

What is the operating voltage for the coil?

The coil operates on 24 VAC at 50Hz. It is crucial to supply the correct voltage to ensure proper function and prevent damage.

How many normally open contacts does this contactor have?

This model (A9C21132) features two (2) normally open (NO) contacts.

Can this contactor be used for direct motor starting?

It is rated for AC-7b applications up to 8.5A, which is suitable for starting small motors. For larger motors, a dedicated motor-rated contactor is recommended.

What does the slider on the side do?

The slider allows for manual operation of the contactor, enabling you to switch the contacts ON or OFF without energizing the control coil. This is useful for testing or maintenance.

What is the lifespan of the electrical contacts?

The electrical lifespan is rated for 100,000 cycles for AC-7A/AC-1 applications.

How much space does it take up on a DIN rail?

It occupies two modular spacings, which typically equates to 36mm (2 x 18mm) on a standard DIN rail.

Is this product suitable for outdoor use?

No, the iCT contactor has an IP20 rating, meaning it is protected against solid objects but not against water or dust ingress. It should be installed in a suitable enclosure.

Troubleshooting

Contactor does not switch when control voltage is applied.

Verify the control voltage is exactly 24 VAC and applied to the correct coil terminals (A1/A2). Check for any obstructions preventing the armature movement. Ensure the manual slider is not engaged in the manual 'ON' position if remote control is expected.

Contacts are welded or stuck open/closed.

This indicates a potential overload or electrical fault. Disconnect power immediately. Inspect contacts for damage. If contacts are damaged, the contactor will need replacement. Ensure the load current does not exceed the rated limits (25A AC-7a / 8.5A AC-7b).

Overheating of the contactor.

Check if the load current exceeds the contactor's rating for the specific application type (AC-7a or AC-7b). Ensure adequate ventilation around the contactor within the enclosure. Loose wiring connections can also cause overheating.

Pros and Cons

Pros

  • Reliable remote and manual control options.
  • Suitable for diverse control applications (lighting, small motors, HVAC).
  • Long electrical lifespan for extended service.
  • Easy DIN-rail installation and integration with Acti9 system.
  • Robust construction from a reputable brand.

Cons

  • Requires a specific coil voltage (24 VAC) which must match the control circuit.
  • Limited to 2 normally open contacts.
  • Not suitable for heavy-duty industrial motor starting.
  • IP20 rating means it requires enclosure protection against dust and moisture.

Setup, Compatibility & Care

Setup: Mount the iCT contactor onto a standard 35mm DIN-rail. Connect the control circuit wires to the coil terminals (typically marked A1/A2). Wire the load circuit through the two normally open (NO) contacts. Ensure the control voltage supplied to the coil is 24 VAC, 50Hz, matching the product specifications.

Compatibility: This contactor is fully compatible with all Schneider Electric Acti9 control accessories and other Acti9 modular devices. Ensure your control circuit voltage is 24 VAC.

Care: The iCT contactor is designed for low-maintenance operation. Keep the surrounding area clean and free of dust. Periodically inspect wiring connections for tightness. No internal cleaning is typically required for standard applications.