Setup, Compatibility & Care
Setup:
- Ensure power to the motor circuit is de-energized.
- Mount the GV2P20 breaker onto a suitable DIN rail or panel according to manufacturer guidelines.
- Connect the three power input terminals to the incoming power supply.
- Connect the three output terminals to the motor.
- Adjust the thermal trip setting using the rotary dial to match the motor's full load current (FLA), typically between 13A and 18A for this model.
- Ensure the rotary handle is properly attached and accessible for operation.
Compatibility:
This breaker is designed for 3-phase AC motor circuits. Ensure your motor's power rating (up to 7.5kW at 400V) and operating current fall within the breaker's specifications (13-18A thermal, 13xIn magnetic trip).
Care:
- The device has an IP20 rating, meaning it is protected against solid objects greater than 12.5mm but offers no protection against water. It must be installed in an enclosure (e.g., control panel) to protect it from dust, moisture, and physical contact.
- Periodically inspect the terminals for tightness and signs of corrosion.
- Keep the breaker clean and free from excessive dust accumulation.