Schneider Electric TeSys Island - TPRST009

This Schneider Electric TeSys Island SIL starter, model TPRST009, is designed for direct connectio...

Best current price£86.94from eBay

All Offers

7 offers from £86.94 - £1,385.84

View price history by clicking the chart icon.

eBayDOL TeSys Island Starter Module I=9A (AC-3)/ 4kW TPRST009
£13.20 delivery
£86.94
Visit shop
Tameson UKSchneider Electric Tesys Island Fieldbus Decentralized Peripheral - Circuit Breaker/Power Switch - Tprst009
Free delivery in 1–3 days
£107.91
Visit shop

Used Offer

1 offer from £51.65

View price history by clicking the chart icon.

eBaySchneider Electric Direct Starter TPRST009 Motor Starter 9 A 4 kW TeSys Unit
£30.56 delivery
£51.65
Visit shop

Product Information

Full details

The Schneider Electric TeSys Island TPRST009 is a Direct On Line (DOL) SIL starter designed for industrial automation. It's ideal for users needing robust motor control, protection, and monitoring within an intelligent electrical system. A key benefit is its direct connection to automation controllers via a bus coupler, simplifying wiring. However, it requires a bus coupler and a voltage module (TPRVM) to be fully operational, representing a significant initial setup dependency.

All features

SeriesTeSys Island
Model Part NumberTPRST009
BrandSchneider Electric

Extended Product Information

FAQs

What is required for the TPRST009 to operate?

The TPRST009 requires connection to a Schneider Electric TeSys Island bus coupler (e.g., TPRBC) and a voltage module (e.g., TPRVM) to be fully operational.

What types of motor protection does this starter offer?

It offers comprehensive protection including thermal overload, overcurrent, undercurrent, jam, long start, stall, phase sequence, phase loss, phase reversal, phase unbalance, and ground current protection.

Can I use this starter for manual control directly?

No, the TPRST009 is designed to be controlled and monitored via an automation controller through a bus coupler. It does not have direct manual control inputs.

What is the maximum power rating for this starter?

The starter has a power rating of 5.5 kW for DOL applications at 690V AC.

Is this starter suitable for safety-critical applications?

Yes, the TeSys Island SIL starter is designed for integration into functional safety systems and is certified to relevant IEC and ISO standards (e.g., SIL 2, PL d).

How is the starter configured?

Configuration is performed digitally using the TeSys Island system software or the dedicated TeSys Island Configurator tool. There are no physical dials or switches.

What fieldbuses are supported?

When used with a compatible bus coupler, it supports EtherNet/IP, Modbus TCP, PROFINET, and PROFIBUS.

Troubleshooting

Starter not powering on or communicating

Verify the connections to the TeSys Island bus coupler and ensure the bus coupler is powered and configured correctly. Check that the voltage module (TPRVM) is properly installed and connected.

Motor overload fault without apparent cause

Check the motor's actual current draw against the configured thermal protection range. Ensure the motor is not mechanically jammed and that the load is within specifications for the starter and motor.

Communication errors with the automation controller

Confirm the fieldbus connection (EtherNet/IP, Modbus TCP, PROFINET, etc.) is secure and correctly terminated. Verify the IP address or device address configuration in both the TeSys Island system and the controller.

Inaccurate energy monitoring readings

Ensure the TPRVM voltage module is correctly installed and calibrated. Verify that the voltage and current measurements within the system configuration match the actual supply and load conditions.

Pros and Cons

Pros

  • Seamless integration into Industry 4.0 environments.
  • Comprehensive protection and monitoring capabilities.
  • Reduced wiring complexity due to bus coupler connectivity.
  • Enhanced functional safety features with SIL certification.
  • Digitized control eliminates manual adjustments and reduces errors.

Cons

  • Requires a bus coupler (e.g., TPRBC) to function.
  • Requires a voltage module (e.g., TPRVM) for full monitoring features.
  • Initial setup complexity due to system dependency.
  • Limited to 80A current rating, may not suit very high-power applications.

Setup, Compatibility & Care

Setup: The TPRST009 starter base must be connected to a compatible TeSys Island bus coupler (e.g., TPRBC) and a voltage module (TPRVM) to become operational. Power is supplied via the bus coupler. All configuration and parameter settings are performed digitally through the TeSys Island system software or the TeSys Island Configurator tool.

Compatibility: This starter is part of the TeSys Island ecosystem. It supports major fieldbuses such as EtherNet/IP, Modbus TCP, PROFINET, and PROFIBUS when used with the appropriate bus coupler. It is designed for DOL motor starting up to 5.5 kW at 690V AC, 1 or 3 phases.

Care: The enclosure has an IP20 rating, meaning it is protected against solid objects greater than 12.5mm but offers no water protection. Ensure the unit is installed in a clean, dry environment, free from excessive dust or moisture. Periodic visual inspection for any signs of damage or loose connections is recommended. No mechanical maintenance is typically required due to its digital nature.